Anonymous
I bought an MBE1224B100BTS I should be able to isolate my neutral with this panel. Please help my inspector its telling mye I cant use this panel as a sub panel. Im only the home owner.
Hi! Thank you for posting your query about the Cutler-Hammer MBE1224B100BTS. This meter socket load center has the neutral bonded with the ground for service entrance. No, it cannot be used as a sub panel. For sub panel suggestions, you can have the Eaton BRP12L125G with 125 AMP for an indoor application and the Eaton BR1224L125RG with 125 AMP for an outdoor application. You can purchase any sub panel as long as it is without the meter socket. Please click MBE1224B100BTS to see the illustration. We hope this helps. Should you need further assistance, please let us know. Thank you!